Daily maintenance and precautions for low nitrogen burners:
1. It is recommended to clean the filter screen in the oil pump every three months. If the oil pump filter screen is found to be dirty, the filter screen at the rear end of the oil nozzle also needs to be cleaned.
2. The fuel tank is cleaned once a year.
3. The best working time of the nozzle is 1000 hours. In order to reduce energy consumption and ensure combustion quality, it is recommended to replace it once a year.
4. After a period of use, the combustion head of the burner and the impeller of the fan will accumulate dirt, which should be cleaned regularly according to the cleanliness of the combustion.
5. The burner always keeps the surface of the equipment clean. The vicinity should be kept clean, and flammable and explosive items should not be stacked.
6. If the oil supply pipe is found to be leaking, it must be properly repaired before continuing to use it. At the same time, it is necessary to maintain a dry working environment near the burner.
7. Too high, too low or unstable voltage will cause damage to some components of the burner, and even reduce the safety guarantee provided by the control box when checking the combustion.
8. The design and installation of the chimney should avoid strong outdoor wind from blowing back into the furnace, and the flue should be cleaned regularly.
9. When the burner is burning, it needs a certain volume of fresh combustion air.
10. Don't start the burner frequently, and it takes at least 3 minutes for each start.
11. Monitor the differential pressure gauge reading at any time during the use of the burner. When the operating pressure difference reaches 0.02Mpa, the filter element should be flushed. If other abnormalities occur, professional maintenance personnel should be notified in time.
12. When the equipment is stopped, lubricate each rotation of the quick-opening blind plate (flange cover) in time according to the regulations. The lead screw of the opening and closing parts should be coated with grease. Other parts should also be coated with grease. For those that cannot be lubricated For grease parts, 10# or 20# oil can be injected.
13. Periodic inspection of this equipment must be carried out in strict accordance with relevant regulations. Carry out a comprehensive inspection of the equipment at least once a year, the measurement of the wall thickness of the equipment, and the non-destructive testing of the pressure welding seam of the equipment every two years. All inspection and testing results shall be recorded in the technical file of the equipment.
14. When there is pressure inside the ultra-low nitrogen burner equipment, no maintenance shall be carried out.
15. When the equipment is parked, the liquid in the equipment should be drained, the surface of the equipment should be thoroughly cleaned, all rotating parts should be coated with anti-grease, and the equipment should be covered with canvas to prevent dirt from depositing on the surface of the equipment.